▪ Conventional Panel
– Can be main Panel – AS7240.
– or CIE where other panel is main.
– If CIE solid door installed.
▪ Detection available as 2 or 8 zone.
▪ FirePro Circuits are fully monitored.
▪ Mimic Panel – Status of FP Units.
▪ Activation-ISOLATE switch on Panel
▪ Max 80 FirePro Units per Gas Card
▪ 2 types of Detection – smoke/heat
– configure for Dual Knock activation.
– dont mix types in a detector circuit.
▪ SHUTDOWN of systems required:
– air conditioning.
– power in Battery systems.
▪ Complies to AS 4487 and AS 1670 |
▪ Uses 485 Bus Communications.
▪ MAX of 7 Devices on serial comms.
▪ MAX of 3 Devices on Status Power.
▪ Cant use 24v AUX on Gas Module.
▪ Cant use T-connections on 485 bus.
▪ Each Device – separate address.
▪ More than 7 – mimic connections.
|
|
|
Allow for maintenance.
▪ Locate clear of mechanical-weather.
▪ Use of HD brackets.
▪ Minimum clearances for FP Units.
▪ Means of egress or rescue. |
Cable install is critical.
▪ Consider Cable path.
▪ Use screened cable for FP Units.
▪ Use conduit where exposed. |
▪ Replaces Press.switch. System “Released”
▪ Mount to FP unit closest to Panel.
▪ Fuse is a normally CLOSED Circuit.
▪ Require setting change on Panel. |
▪ Test Module connected first.
▪ Plug directly to panel.
▪ Isolates all downstream units.
▪ Runs on 9v Battery. |